** Replacement for models LGB21.130A27 and LMG21.130B27
The LME21.130C2 is used for the startup and supervision of 1- or 2-stage gas or gas/oil burners in intermittent operation. The flame is supervised by an ionization probe or flame detector QRA... with ancillary unit AGQ3...A27 for gas/oil forced draft burners or blue-burning flames with blue-flame detectors QRC... In terms of housing dimensions, the LME... are identical with the burner control LGB... and LMG... burner controls
Specifications:
- Ref. LME21.130C2 - Undervoltage detection - Air pressure supervision with functional check of the air pressure switch during startup and operation - Electrical remote reset facility - Multicolor indication of fault status and operational status messages - Limitation of the number of repetitions - Accurate control sequence thanks to digital signal handling - Controlled intermittent operation after 24 hours of continuous operation - Flame detectors: ionization probe or detector QRA ... with ... AGQ3 A27 - Burner controls for 2-stage burners, without actuator control - Power supply: AC 230V