Description
Dynamic self-checking flame detector C7061F used with R7861 Dynamic Self-check Amplifiers for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels.
Specifications:
- Application: Gas and oil fired burners .
- Electrical Connections: Terminal block.
- Complete reference: C7061F2001
- Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor to provide the UV sensor tube checking function.
- Can be mounted horizontally, vertically or at any angle in between.
- The detector requires faceplate alignment and has integral locating reference points to assure proper operation of the shutter mechanism.
- Field replaceable ultraviolet sensing tube and quartz viewing window.
- Two detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
- Protective heat block built into mounting flange.
- Type: Ultraviolet, Purple Peeper, Dynamic Self-Checking .- Application: Gas and oil fired burners .
- Electrical Connections: Terminal block.
- Mounting: 1 in. NPT
- Range temperature: -40 to +79ºC
- Lead length: 2438 mm
- NEMA range: explosion proof
Reference |
Voltage Vac/ Frequency Hz |
C7061F1003 |
OBSOLETE |
C7061F2001 |
120 / 50, 60 |
Related products