Flame detector |
Reference |
Approved in: |
tw/s ca |
t1/s min. |
TSA/s max. |
t3n/s ca. |
t3/s ca. |
t4/s |
t9/s 6)max. |
t10/s mín. |
t11/s 3) max. |
t12/s 3) max. |
t20/s ca. |
||||||||
Burner controls for 2-stage burners without control of actuator |
|||||||||||||||||||||
Ionization
probe (ION) or UV detector QRA... with AGQ1...A27 |
LGB22.130A27 4) |
CH, EU, N, S |
9 |
7 |
3 |
2.4 |
3 |
8 |
--- |
4 |
12 |
12 |
21 |
||||||||
LGB22.230B27 5) |
CH, EU, N, S, SF |
9 |
20 |
3 |
2.4 |
3 |
8 |
--- |
4 |
16.5 |
16.5 |
2 |
|||||||||
LGB22.330A27 5)7) |
AUS, CH, EU, H, N, S, SF |
9 |
30 |
3 |
2.4 |
3 |
8 |
--- |
4 |
12 |
11 |
2 |
|||||||||
LGB22.330A270 5)8) |
EU |
9 |
30 |
3 |
2.4 |
3 |
8 |
--- |
4 |
12 |
11 |
2 |
tw |
Waiting time |
|
|
t1 |
Prepurge time |
|
|
TSA |
Ignition safety time |
|
|
t3 |
Preignition time |
4) |
Also suited for flash steam generators |
t3n |
Postignition time |
5) |
Also suited for stationary direct-fired air heaters |
t4 |
Interval fuel valve (BV1) –
fuel valve (BV2) or |
|
|
|
fuel valve BV1) – load
controller (LR) |
7) |
Also available for AC 100...110 V; |
t9 |
2nd safety time |
|
last digits ...17 in place of ...27 |
t10 |
Specified time for air pressure signal |
8) |
Without internal microfuse; must to be used in connection with |
t11 |
Programmed opening time for actuator (SA) |
|
external microfuse 6.3 A (slow)! |
t12 |
Programmed closing time for actuator (SA) |
|
|
t20 |
Interval up to self-shutdown of programming mechanism |
|
|