Description
The automatic safety burner control MMI 962.1 controls and supervises blown gas- and combined burners of any nominal thermal load (tested and certified according to EN 298). Together with an air damper motor, a 2-stage burner with 2 fuel valves or a modulating system ave possible.
Specifications:
- Complete reference: MMI 962.1 mod. 23 (06256U Honeywell)
- For power gas burners, with terminals for air damper motor and built-in remote reset for lock-outs.
- Flame detection: ionisation probe, infrared-flicker detector IRD 1020.
Model |
Max. Reaction time for air
proving switch tlw |
Supervised pre-purge time tv1 |
Air damper open signal prepurge
tlk |
Pre-ignition time tvz |
Waiting time start tw |
Safety time ts |
Ignition time tn |
Delay 2nd-stage tv2 |
Power supply |
23 (06256U) |
15 |
30 |
38 |
3 |
8 |
3 |
6.6 |
8 |
220-240 V |