DBC2000E1000 Honeywell

HONEYWELL FLAME CONTROL
Industrial 115Vac digital burner controller with integrated FR/UV flame amplifier
Stock 1 units
Delivery:
24-48h
573.00
573.00 Taxes not included
Calculate the shipping costs
Select country and zip code to calculate the shipping costs
The Honeywell DBC2000E1000 is digital industrial 115Vac burner controller with integrated FR/UV flame amplifier.


Honeywell Burner Controls DBC2000-series
The Honeywell DBC2000 is a microprocessor-based integrated burner controller for automatically fired gas, oil or combination fuel industrial single burner power burner applications. The DBC2000 system consists of the relay module and wiring subbase. The Standard Model provides the minimum requirements to control an industrial burner system; the Enhanced Model includes an integrated Valve Proofing System; the Ultimate model includes bus communication on top of this.

For all type of burners with unlimited capacity in intermittent operation. An integrated timer assures an automated recycle sequence after ca 24h uninterrupted heat demand.

Approvals:
CE approved according EN298 for intermittent operation (when used with correct flame sensor).
AGA certified

Protection class: IP40
Ambient temperature: -10...60C
Maximum humidity: 90%rh

DBC2000 models have two integrated flame amplifiers: UV Power Tube (UV) and Rectification (FR), that are selectable by a jumper at the back of the unit. Default is FR (jumper present).
Applicable flame sensors:
Flame rod (FR)
UV sensor family C7027/35/44 (UV)
UV sensor family C7012A/G (FR)
IR sensor family IRD820/1020 (FR)
Note: Extra features:
Integrated 24h auto recycle timer
Selectable Pilot or Direct Main Burner Ignition operation.
Selectable post-purge (15s) or no-post-purge (0s) operation.
Control model: Full
Outputs: HF/LF/Modulate
Operation: 24h auto-recycle
Pilot: Selectable intermittent / interrupted
Pilot ignition time: 3s (Pilot only: 5s)
Main ignition time: 3s
Post purge time: 15/0s
Number of ignition attempts: 1
Flame failure response time: <1s
Flame detector: UV/FR

115Vac versions
Prepurge time: 35s
Valve proofing system: no
Comment: Standard Model