The automatic safety burner control MMI 810.1 controls and supervises blown gas- and combined burners of any nominal thermal load (tested and certified according to EN 298).

Specifications:

- Complete reference: MMI 810.1 mod. 33 (0620220U Honeywell)
- For 2-stage forced draught, combi oil/gas burners and for burners on fixed hot air heaters (Direct air heaters according to DIN 4794)
- Flame detection: ionization probe, infrared-flicker detector IRD 1020.


Model

Max. Reaction time for air proving switch tlw

Supervised pre-purge time tv1

Pre-ignition time tvz

Waiting time start tw

Safety time ts

Ignition time tz

Delay 2nd-stage tv2

Power supply

Mod. 33 (0620220U)

6

24

3

9

3

6

10

220-240 V