M7284Q1106 Honeywell

HONEYWELL FLAME CONTROL
Modutrol Actuator 24V Non-Spring Return Foot Mounted Actuator with 150 lb-in. torque, 4-20 mA.

OBSOLETE MODEL. CONSULT US POSIBLE REPLACEMENT.
Immediate delivery not available
Delivery:
OBSOLETE. CONSULT US REPLACEMENT
Calculate the shipping costs
Select country and zip code to calculate the shipping costs
OBSOLETE MODEL. CONSULT US POSIBLE REPLACEMENT.

Series 72 Modutrol IV Actuators are spring return and non-spring return motors (per motor type) used to control dampers and valves. The motors accept a current or voltage signal from an electronic controller to position a damper or valve at any point between open and closed.

Description: Modutrol IV™ Electric Motor.
Internal Auxiliary Switch: 2.
Fail Safe Mode: Non-Spring Return.
Control Signal: Modulating, 4-20 mA.
Feedback: No.
Motor shaft: Dual-ended shaft
Stroke: Adjustable; 90 to 160 degrees, Symmetrical.
Torque Rating: 17 Nm 150 lb-in.
External Auxiliary Switches Available: Yes.
Voltage 24Vac 50/60 Hz 15 VA
Electrical Connections: Screw terminals.
Shaft Shape/Dimensions: square / 10 mm.
Mounting: Foot-mounted.
Weight: 3.5 kg.
Dimensions: 164 mm high x 140 mm wide x 185 mm deep.
Temperature Range, Ambient: -40 to +60 ºC.
Nominal Timing: 30-60 sec.
Shaft Rotation (upon control signal increase): Clockwise (as viewed from power end) (normally closed)
Approvals: CE EN55011 (Emission) EN50082-2 (Immunity) 73/23/EEC (LVD)
Comments: Adjustable zero and span for split range applications.

• Integral spring return returns motor to normal position in the event of power failure on spring return models.
• Integral junction box provides NEMA 3 weather protection if motor is mounted in the upright position.
• Adapter bracket for matching shaft height of older motors is available.
• Spring return motors can operate valve linkages from power end or auxiliary end shafts for normally closed or normally open valve applications.
• All models have dual shafts (slotted and tapped on both ends).
• All models have auxiliary switch cams.
• Fixed torque throughout the entire voltage range.
• Motors are designed for either normally open or normally closed valves and dampers.
• Die-cast aluminum housing.