LMO14.111C2 Siemens

SIEMENS FLAME CONTROL
Flame controller Siemens for use with oil burners.
Stock 2 units
Delivery:
24-48h
58.50
58.50 Taxes not included
Calculate the shipping costs
Select country and zip code to calculate the shipping costs
Flame controller LMO14.111C2 microcontroller-based, designed for the startup and the supervision of 1- or 2-stage forced draft oil burners in intermittent operation. Yellow-burning flames are supervised with photo resistive detectors QRB..., blue-burning flames with blue-flame detectors QRC...


Specifications:

- Complete reference: LMO14.111C2
- Oil burners with fans to EN 267 
- Burner controls for use with atomization oil burners of monoblock design to DIN EN 230:2005-10 
- LMO44... for use with stationary direct-fired air heaters 
- Undervoltage detection 
- Electrical remote reset 
- Bridging contact for oil preheater 
- Monitoring of time for oil preheater 
- Accurate and reproducible control sequence thanks to digital signal handling 
- Controlled intermittent operation after 24 hours of continuous operation 
- Limitation of the number of repetitions 
- Multicolor indication of fault status and operational status messages
- Power supply: AC 230V
- Fuel valve stages: 1
- Burner capacity: < 30kg/h

** Comparable burner controller (LMO... can replace LOA...): LOA24.171B27  LOA26.171B27  LOA36.171A27