Description
Rectification amplifier R7847A responds to the inputs of a flame detector Honeywell to indicate the presence of flame when used with relay modules of the 7800 series.
Specifications:
- Complete reference: R7847A1025, R7847A1033, R7847A1074, R7847A1082
- Flame signal strengh ranges between 0.0 and 5.0 VDC.
- Temperature range: -40 °C to 60 °C
Reference |
Detection type |
FFRT (sec) |
Controller |
Color |
Detectors |
R7847A1025 |
Rectification |
0.8 - 1 |
Serie 7800 |
Green |
Gas: rectifying C7004, 5, 7, 8,
9, Q179 |
R7847A1033 |
2 - 3 |
Gas: rectifying C7004, 5, 7, 8,
9, Q179; gas, oil, coal, ultraviolet C7012A/C |
|||
R7847A1074 |
0.8 - 1 |
Gas: rectifying C7004, 5, 7, 8,
9, Q179, for impedance for leadwire > 50' or ultraviolet detector C7012A/C |
|||
R7847A1082 |
2 - 3 |
Gas: rectifying C7004, 5, 7, 8,
9, Q179, for impedance for leadwire > 50' or ultraviolet detector C7012A/C |