Description
The Satronic TMG 740-3 burner control box is capable of controlling and monitoring medium to high performance forced draught and dual fuel oil/gas burners in single or two stage versions. It can be used, as prefered, for multi-stage or modulating operation with burners of any nominal rating as well as in direct air heaters.
- Complete reference: TMG 740.3 mod. 32-32 (08211U Honeywell), TMG 740.3 mod. 43-35 (08218U Honeywell)
- For high performance forced draught and dual fuel burners in intermittent operation (single or two stage versions).
- For high performance forced draught and dual fuel burners in intermittent operation (single or two stage versions).
- Power supply: 220 Vac 50/60 Hz.
- Suitable flame detectors: ionisation probe, UV sensor, infra-red flicker detector
Model |
Pre-purge time supervised |
Pre-purge time with air damper
open |
Pre-ignition time fixed |
Start valve safety interval |
Pilot valve safety interval |
Pilot valve switch on time |
Main valve 1 safety interval |
Valve 1 delay |
Valve 2 delay |
Post-purge |
32-32 (08211U) |
24 |
30 |
3 |
2 |
3 |
11 |
2 |
9 |
6 |
7 |
43-35 (08218U) |
32 |
40 |
4 |
3 |
3 |
14 |
5 |
10 |
10 |
10 |
Related products